Simple, Effective Reservoir Control

Cla-Val
Cla-Val Simple, Effective Reservoir Control

Simple, Effective Reservoir Control

By: Cla-Val

Boars Head Service Reservoir provides fresh drinking water to just under 6,000 customers across 3 DMA’s near Wigan, Lancashire. The site had been operating for a number of years using a 12″ (300mm) actuated butterfly valve to control the tank inlet water supply to control at a pre-determined minimum and maximum water level.

The site does not have accurate flow metering and so the valve operation was spindle % position only, the levels were controlled manually by a United Utilities operator continually adjusting the % position. This proved very challenging and time consuming, plus there is a second reservoir fed from the same system that Boars Head has an impact on balancing level.

Cla-Val Simple, Effective Reservoir Control (2)

The site also experienced a history of pressure transients due to rapid changes in flow velocity based by uncontrolled actuator movements. Due to limitations in valve design UU were struggling to control levels accurately and consistently and wanted to explore an automated and effective method of operation and provide a diurnal level control pattern whilst managing water turnover.

Cla-Val Simple, Effective Reservoir Control (1)

United Utilities approached Cla-Val to explore what solution could be sought. Listening to their issues Cla-Val was able to help, plus retain the use of the existing valve by installing the Cla-Val VC-22D Controller.

Cla-Val Simple, Effective Reservoir Control (3)

Onsite actuator motor assembly and VC-22D Controller

Reservoir Management

  • No Flowmeter required
  • Default position % on loss of level signal
  • Network Calming approach Utilizes existing asset
  • Removes pressure transients
  • No water quality risks

The VC-22D Controller provides site-specific Valvapps. In this application, Cla-Val used a ‘fill & drain Valvapp’ to automatically control levels between a pre-set range. By taking the 4-20mA reservoir level signal back to the VC-22D Cla-Val were able to program a minimum and maximum level threshold (between 11.48 ft (3.5m)hd and 18 ft (5.5m)hd) and create two % values to output to the valve actuator to facilitate filling and draining of the tank (1% to drain and 5.5% to fill).

By using the VC-22D Controller were able to offer a complete solution.

  1. Remove transient behavior – by ramping actuator % to ensure open and close action was slow and smooth (1% per minute)
  2. Provide a diurnal level pattern across a 7-day period by utilizing preprogrammed fill and drain %
  3. Provide water turnover – level HI and LO thresholds
  4. Drives actuator to default % on level signal failure

Related Articles

Cla-Val Pukaki Irrigation Scheme

Pukaki Irrigation Scheme

The Mackenzie Country or Mackenzie Basin is a wide valley between the mountain ranges of the Southern Alps, namely the…

Related Whitepapers

Design Optimization of Jet Fuel Pump for Aviation

Jet fuel pumps play a critical role in the safe and efficient operation of commercial aviation. The performance and reliability of these pumps directly impact…

The Cost Of Downtime In Manufacturing [Infographic]

Downtime can be the most expensive element of any manufacturing operation. Here are some important facts and tips you should know to cut down on…

AFT Fathom used to Model Central Heating Cycle of a State-of-the-art Combined Heat and Power Plant

Kerem Algüzey, design engineer at ENKA Insaat ve Sanayi A.S., used AFT Fathom to simulate the central heating cycle to inform the design of the…

Driving Energy Savings a Commercial Facility Energy Upgrade Project

Upgrading to Design Envelope pumps helped GAC save energy costs of 20,000 AED in the first year. Armstrong’s Pump Manager service provides reports and notifications…

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *