Tips for Testing Your Motors: Motor Circuit Analysis (MCA™)

ALL-TEST Pro
ALL-TEST Pro

Tips for Testing Your Motors: Motor Circuit Analysis (MCA™)

Contributor: ALL-TEST Pro LLC

When a de-energized Motor Circuit Analysis (MCA™) motor testing program is first implemented, it is not unusual to have between 10-30% of the motor systems tested to exhibit one or more alarm condition(s) when testing is performed from the output of the motor starter or motor drive. When a motor system is in an alarm condition, this does not necessarily mean that the motor will fail or that it should be stopped immediately, but that the measured values have exceeded pre-determined limits.

One of the first considerations should be motor criticality. Obviously, the most critical motors should be afforded a higher priority than less critical motors. The second consideration is the type and location of the alarm (is it related to the connections, cable, motor winding, etc.?)

It is important to note that a motor system exhibiting an alarm condition should not be automatically condemned or the motor replaced, if the test was performed from the motor control center (output of the motor starter or motor drive). Motor connections and cables between the test point and the motor itself may be the root-cause of the alarm.

Therefore, the next step is to perform another test at the next connection point, whether a disconnect or at the motor itself, with incoming phase leads disconnected. If the alarm condition clears, then the problem is upstream of the test point. If the alarm persists, then it is the motor. Lastly, non-repeatable test results should be considered suspect and investigated further.

With respect to AC induction squirrel-cage rotor motors <1000V, many new motors will exhibit an inductance and impedance imbalance; due to motor design/construction. Therefore, a healthy motor can exhibit an impedance and inductance alarm, even though it is in good condition. Motor Circuit Analysis measurements include impedance and inductance measurements, but phase balance is not used for assessing the condition of the motor windings.

Learn How to Diagnose Motor, Generator, and Transformer Faults

Related Articles

ATP

Why Test Motors?

Because Motors Fail! Not all winding faults start as ground faults. Instead, they can start as a weakness in the winding…

Related Whitepapers

Most Common Rib Designs for Heat Exchanger Gaskets

There are many styles of heat exchanger gaskets and most have complicated rib designs or partitions. In this document from Durlon® Sealing Solutions, download some…

Test Methods to Qualify Quarter-Turn Valves for Low Emissions Service

Author: Phil Mahoney FSA Member, A.W. Chesterton Co. Currently, two test procedures could be requested to qualify a quarter-turn valve design for fugitive emissions service:…

How To Troubleshoot A Magnetic Drive Centrifugal Pump

Magnetic drive pumps are a great alternative to traditional mechanically sealed pumps especially when pumping corrosive, dangerous, or expensive fluids.  While usually categorized as a…

Check Valve Sizing is More Important Than You Think

It is surprisingly common for check valve sizing to be an afterthought in the flow control/fluid process industries. Often marketed together with gate and globe…

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

Sign up for our Newsletter


By submitting this form, you are consenting to receive marketing emails from: Empowering Pumps & Equipment, 2205-C 7th Street, Tuscaloosa, AL, 35401, http://www.empoweringpumps.com. You can revoke your consent to receive emails at any time by using the SafeUnsubscribe® link, found at the bottom of every email. Emails are serviced by Constant Contact