Motor Circuit Analysis Testing

ALL-TEST Pro
ALL-TEST Pro

Motor Circuit Analysis Testing

When a winding fault is detected from the motor control center or disconnect using MCA, a test must be performed at the motor. As motor circuit analysis measurements of Test Valve Static, phase angle and current/frequency response, and insulation to ground can detect cable faults as well.

ALL-TEST Pro

De-Energized Testing in Place

If the winding tests good at the motor, then the cable has a fault. If the test improves but the fault still shows, it is both a cable and winding fault; and if the test shows the same results as the motor, the fault is in the stator windings.

 

Related Articles

ATP

Why Test Motors?

Because Motors Fail! Not all winding faults start as ground faults. Instead, they can start as a weakness in the winding…

Related Whitepapers

Pump Maintenance Mistakes Checklist

A pump is an expensive piece of any water system. Maybe not the most expensive, but certainly not the least. However, only a small fraction…

Selecting the Right Bearings to Improve Vertical Turbine Pump Reliability

Selecting the Right Bearings to Improve Vertical Turbine Pump Reliability Vertical Turbine Pumps (VTPs) are available in a variety of configurations and are used for…

Torque Measurement Precision: Why the Overload vs. Overrange Distinction Matters for Quality Control

Why properly understanding and differentiating between overload and overrange helps to maintain the accuracy and longevity of the torque meter. Two easily overlooked, yet extremely…

Implementing Predictive and Prescriptive Digital Maintenance Technologies for Rotating Equipment

Business and operations systems are becoming increasingly integrated in the digital era. With accessible data and information, enhancing the business value of plants that utilize…