Motor Circuit Analysis Testing

ALL-TEST Pro
ALL-TEST Pro

Motor Circuit Analysis Testing

When a winding fault is detected from the motor control center or disconnect using MCA, a test must be performed at the motor. As motor circuit analysis measurements of Test Valve Static, phase angle and current/frequency response, and insulation to ground can detect cable faults as well.

ALL-TEST Pro

De-Energized Testing in Place

If the winding tests good at the motor, then the cable has a fault. If the test improves but the fault still shows, it is both a cable and winding fault; and if the test shows the same results as the motor, the fault is in the stator windings.

 

Related Articles

ATP

Why Test Motors?

Because Motors Fail! Not all winding faults start as ground faults. Instead, they can start as a weakness in the winding…

Related Whitepapers

Implementing Predictive and Prescriptive Digital Maintenance Technologies for Rotating Equipment

Business and operations systems are becoming increasingly integrated in the digital era. With accessible data and information, enhancing the business value of plants that utilize…

Building a Centrifugal Pump Digital Twin for a Chemical Plant

A digital twin represents a physical asset and its function; it contains intelligence to evaluate static and real-time data. Chemical refining plants are asset intensive…

Autonomous Fontan pump: Computational feasibility study

A double-inlet, double-outlet rotary pump was designed to augment Fontan flow through the total cavopulmonary connection. Pump power is supplied by a systemic arterial shunt…

Hydraulic design of a centrifugal LOX pump, including cavitation modeling

The study shows the design and optimization of a LOX centrifugal pump with CFturbo/CFturbo BLADERUNNER 2025.R1 for a fictional rocket engine powered by LOX/RP-1, which…