AFT™ Fathom Determines Cause of Failures: Emergency Cooling Water Ride-through System

Applied Flow Technology
AFT™ Fathom Determines Cause of Failures Emergency Cooling Water Ride-through System Swanson Rink

AFT™ Fathom Determines Cause of Failures: Emergency Cooling Water Ride-through System

Swanson Rink
Denver, Colorado, USA
Platinum Pipe Award Winner – Operational Benefits and Sustainability

Swanson Rink was tasked with developing a chilled water distribution system in an undisclosed data center, along with a method of providing cooling for a period of time (ride-through) if the central chilled water plant was off line for some reason. The ride-through will provide cooling for the data center for 30 minutes allowing the generator plant to start and also for the chillers to restart in the event of things such as power failure, tornadoes, etc. When the chillers are restarted and are providing chilled water to the data center cooling systems again, the storage tanks are full of warm water. At this point a set of valves open, and a small capacity charging pump starts to divert a small amount of chilled water from the main system to the storage tanks to recharge them, returning the system to its pre-emergency condition.

When engineers commissioned the cooling water storage tanks for the emergency ride-through scenario, one tank experienced unexpected negative pressure and failed, caving inwards (see Figure 1). Engineers suspected the cause to be certain valves not opening correctly, but were not able to rerun any field tests that might damage the system further. Rory Heim, mechanical engineer at Swanson Rink, used AFT Fathom to correlate to physical results seen in the field rather than numerical data.

AFT™ Fathom Determines Cause of Failures Emergency Cooling Water Ride-through System (1)

Figure 2 – AFT Fathom Model: Scenario showing tank overpressurization, triggering relief valves

He used an AFT Fathom model to determine which valve closures would result in the system failures they saw in the field and was able to identify and fix the problems which were difficult to recognize visually because of the orientation of the system components. A similar problem was encountered when recharging the tanks and the AFT Fathom model was used again to identify a valve opening issue that caused a tank to over pressurize and trigger relief valves (see Figure 2).

When asked about the benefits of AFT Fathom, Heim said, “Fathom allowed Swanson Rink to test many scenarios; avoiding further system destruction and with no unintended consequences to the building. Using the Fathom model was much more efficient than running around the mechanical room opening and closing valves to test scenarios. On the day the charging problem was discovered, six people were in the mechanical equipment room for the entire day, running tests and trying to determine the cause of the relief valve activating. Fathom allowed one person to run tests instantaneously, which is a much more efficient use of those six people’s time and the owner’s money.”

Related Articles

Related Whitepapers

Arrow Powers Gas Turbine Analysis at Fern Engineering

Fern Engineering, Inc. was contracted by a major refinery to reduce the exhaust gas temperature variations of their gas turbine fleet. According to Hector Bourgeois,…

2027 DOE Efficiency Mandate & The Case for Higher Efficient Motors

The 2027 DOE motor efficiency requirements are bringing important changes to industrial motor applications. In this presentation, ABB’s Courtney Pickett and Stefanie Casimir break down…

ENKA Designs a State-of-the-Art District Heating System for Hamburg’s CHP Plant

Datacor Fathom provided the best solutions in terms of both heat transfer and pressure loss calculations.” – Kerem Algüzey, ENKA Industry: Power Generation Region: Hamburg,…

Refinery Cooling Water System Calibration Using Datacor Fathom

Hydrus Works, LLC needed to recalibrate a large refinery cooling water system containing nearly 600 pipes, 492 junctions, and 127 heat exchangers. Over 700 pressure,…