AEGIS Rings: Resilience Beyond Resistance

Aegis
AEGIS Rings Resilience Beyond Resistance

AEGIS Rings: Resilience Beyond Resistance

By: Aegis

Installing Colloidal Silver

When an AEGIS ring is installed with colloidal silver on the shaft, the resistance from frame-to-shaft is often under one ohm. Without colloidal silver, it will be higher, perhaps a few ohms. But our engineers have seen installations where fully-functional AEGIS rings’ measured resistance was 30W. The ring was working; the bearings were protected. It’s just that the resistance is not that important.

Shaft voltage is what damages motor bearings when it discharges through them. So it’s the shaft voltage that you should measure to check whether the bearings are at risk.

Using an Oscilloscope for VFD-Controlled Motors

For VFD-controlled motors, you need an oscilloscope to do this. Using a scope with 100 MHz bandwidth or more lets you do two things:

First, it lets you check the maximum shaft voltage level. As a rule, shaft voltage less than 5V peak (10V peak-to-peak) is not a risk for motor bearings. You can check shaft voltage amplitude at timescales between 100 ms and 1 ms per division.AEGIS Rings Resilience Beyond Resistance Second, and more importantly, you can check for discharge at smaller timescales. The smoking gun of discharge through the bearing is voltage building up over a few ms, and then suddenly dropping back to baseline (vertical line). If you check the shaft voltage and don’t see any discharges, then the bearings are not being electrically damaged.

The takeaway is there is no harm in measuring the resistance of an AEGIS ring if you really want to, but the resistance doesn’t tell whether the bearings are protected. For that, you need to measure the shaft voltage with an oscilloscope.

Related Articles

Related Whitepapers

CFturbo BLADERUNNER Centrifugal End-Suction Pump Casestudy

The CFturbo BLADERUNNER 2024 is a unique and innovative tool that will outperform the known capabilities of an automated simulation process for Turbomachinery performance maps.…

Defeat The Enemies That Interrupt Your Water/Wastewater Operation

Download ABB’s new playbook to help you identify and defeat the enemies that interrupt your water/wastewater operation and learn how you can… • Reduce operational…

Sodium Hypochlorite Service Success with NETZSCH PERIPRO®

Sodium hypochlorite (NaOCl) is widely used by municipal water treatment plants Sodium hypochlorite (NaOCl) is an effective water disinfectant to treat the raw, filtered water…

Tips for the Installation of MCRT® Torquemeters

An MCRT® torquemeter must be installed properly as an integral part of a drive line network in order to achieve satisfactory operation. Proper installation will:…

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *